R1-A Rig State
ISOLATED R1-CH chamber R1-G-CH atm FLT-V R1-V-VENT R1-L-VENT R1-V-ISO R1-L-FL R1-P-RP off FLT-EXH atm R1-G-BX ~950 mbar
System Status
R1-V-ISOCLOSED
R1-V-VENTCLOSED
R1-G-CH0.08 mbar
R1-P-RPOFF
Rate-of-Rise Data — R1-G-CH (isolation phase)
0 0.2 0.4 0.6 0 1 2 5 10 time (min) pressure (mbar) decelerating ↗ then flattening
TimeR1-G-CH (mbar)RiseRate (mbar/min)
0 min0.08
1 min0.200.120.12
2 min0.290.090.09
5 min0.440.150.05
10 min0.560.120.024
ModuleM02 RigR1-A CompetencyGas load identification IndicatorInterpret rate-of-rise pattern
⏱ ~10 min
↗ Rate-of-Rise Simulator — S1

Why This Matters

Misreading the pressure rise pattern after isolation can lead to an unnecessary leak investigation — adding hours of diagnostic time when the system is behaving normally.

Situation

R1-A has completed a roughing pumpdown. At t = 0, R1-V-ISO is closed and R1-P-RP is switched off. R1-G-CH reads 0.08 mbar at isolation. Over the next 10 minutes, the gauge reading continues to rise. The technician records the data shown at left and asks: is this normal, or is something wrong?

Your Task — Recognise · Interpret · Communicate · Escalate

  • RecogniseWhat pattern is present in the rate-of-rise data? Is the rate constant, increasing, or decreasing?
  • InterpretBased on this pattern, what is the most likely source of the gas load? Is this normal behaviour or a problem?
  • CommunicateWrite a one-sentence status note summarising your finding, suitable for a shift handover log.
  • EscalateDoes this finding require escalation? If so, what specific information should be included?
💡 Need a clue?

Look at the Rate column — does the number go up, stay the same, or go down as time passes?

📋 Need a guide?

A gas load from the chamber walls is finite — it runs out. A gas load from outside the system (a leak) does not run out. Which type produces a decreasing rate? Which produces a constant rate?

🔢 Step-by-step

1. The rate column reads: 0.12 → 0.09 → 0.05 → 0.024. It is falling each row.

2. A falling rate means the gas source is being depleted. That rules out a real leak (unlimited source).

3. This is outgassing — surface-adsorbed gas desorbing from R1-CH walls under vacuum.

4. Status note: quote starting pressure (0.08 mbar), ending pressure (0.56 mbar), direction of rate (decreasing). Conclude: normal outgassing, no escalation required.

🔒
Debrief & Teaching Points — available after this session
R1-A Rig State
ROUGHING (stalled) R1-CH chamber R1-G-CH atm FLT-V R1-V-VENT R1-L-VENT R1-V-ISO R1-L-FL R1-P-RP running FLT-EXH atm R1-G-BX ~950 mbar stalled 0.35 mbar — normal base 0.05 mbar
System Status
R1-V-ISOOPEN
R1-V-VENTCLOSED
R1-G-CH0.35 mbar (stalled)
R1-P-RPON — normal
Pumpdown Data — R1-G-CH
0 0.35 0.6 0.9 0 2 5 10 time (min) pressure (mbar) stalled 0.35 mbar Expected Today
PhaseExpectedToday
950 → 100 mbar~30 sec~30 sec ✓
100 → 1 mbar~2 min~2 min ✓
1 → 0.1 mbar~5 min20+ min, stalled ✗
ModuleM02 RigR1-A CompetencyContamination identification IndicatorDistinguish contamination from pump failure
⏱ ~10 min
↗ Rate-of-Rise Simulator — S4

Why This Matters

Attributing a contaminated pumpdown to pump failure sends maintenance to the wrong component. The pump is fine — cleaning the chamber is what's needed. Misdiagnosis delays the fix by hours.

Situation

R1-A is in ROUGHING. R1-P-RP is running normally — no unusual noise, vibration, or exhaust odour. R1-V-ISO is open. Yesterday the chamber was opened three times and internal surfaces were handled without gloves during a component swap. Today's pumpdown proceeds normally above 1 mbar, but has been stalled at 0.35 mbar for 30 minutes. Normal base pressure for R1-A is 0.05 mbar.

Your Task — Recognise · Interpret · Communicate · Escalate

  • RecogniseCompare today's pumpdown to expected performance. Where does it deviate from normal?
  • InterpretGiven the system history (multiple chamber openings, ungloved handling), what contamination sources might explain the elevated base pressure? Name at least two.
  • CommunicateWrite a 3-sentence escalation note: (1) what was observed, (2) what the evidence indicates, (3) what additional information is needed. Use specific readings and component IDs.
  • EscalateWhat additional observation would help distinguish between possible contamination sources?
💡 Need a clue?

The pumpdown is normal down to 1 mbar. At what pressure does it diverge? What kind of gas load only appears at low pressures — not at high ones?

📋 Need a guide?

Above 1 mbar, bulk gas dominates — surface contamination has no effect. Below 1 mbar, bulk gas is mostly gone and surface gas load becomes the dominant factor. A stall in the 1–0.1 mbar region points to the surface, not the pump.

🔢 Step-by-step

1. First two pumpdown phases: normal → pump is fine.

2. Stall below 1 mbar → surface gas load region.

3. System history: ungloved handling → fingerprint oil (hydrocarbon). Multiple openings → water adsorption (humid air).

4. Both contamination types raise surface gas load above pump throughput at that pressure — creating a new equilibrium stall point.

5. Escalation note: 0.35 mbar stall; normal base 0.05 mbar; R1-P-RP normal; history of ungloved handling and repeated venting. Need: further pump-down cycling or chamber cleaning.

🔒
Debrief & Teaching Points — available after this session
R1-A Rig State
ROUGHING (post-vent) R1-CH chamber R1-G-CH atm FLT-V R1-V-VENT R1-L-VENT R1-V-ISO R1-L-FL R1-P-RP running FLT-EXH atm R1-G-BX ~950 mbar R1-FLT-VENT — suspected failure locus
System Status
R1-V-ISOOPEN
R1-V-VENTCLOSED
R1-G-CHslow 1→0.1 mbar
R1-P-RPON — normal
Key Evidence
  • Chamber clean before venting — confirmed by visual inspection at start of day
  • Particles appeared after venting and re-seal — before roughing pump restarted
  • R1-P-RP running normally: no change in noise, vibration, or exhaust odour
  • Pumpdown extended in 1–0.1 mbar range: 12 min vs normal 5 min
  • 950–1 mbar pumpdown phase: normal speed (bulk gas removal unaffected)
PhaseNormalToday
950 → 1 mbar~2.5 min~2.5 min ✓
1 → 0.1 mbar~5 min~12 min ✗
ModuleM02 RigR1-A CompetencyContamination source tracing IndicatorLink vent event to particle ingress
⏱ ~10 min
(no sim for this card)

Why This Matters

Particle contamination in a vacuum chamber affects sample quality and pumpdown performance. Identifying the entry point (R1-FLT-VENT) determines the corrective action — a filter check, not a chamber rebuild.

Situation

R1-A was pumped to base pressure successfully this morning. The chamber was then vented using R1-V-VENT and brought to atmosphere for a brief inspection. After re-sealing, ROUGHING was restarted. R1-P-RP is running normally. However, visible particles are now present inside R1-CH that were not there before venting. The pumpdown from 1 to 0.1 mbar is taking approximately 12 minutes — normally it takes 5 minutes.

Your Task — Recognise · Interpret · Communicate · Escalate

  • RecogniseWhen did the particles most likely enter the chamber? What evidence supports your conclusion?
  • InterpretR1-FLT-VENT is designed to prevent particulate contamination during venting. Name at least two explanations for why particles might have bypassed it.
  • CommunicateWhy is the pumpdown extended in the 1–0.1 mbar range after this event? What is the connection between particles and pumpdown performance?
  • EscalateWrite a 3-sentence observation summary: (1) what was observed, (2) what the evidence indicates, (3) what information is needed before the system is used again.
💡 Need a clue?

The chamber was clean before the vent and contaminated after. What happened between those two states? Only one event occurred.

📋 Need a guide?

R1-FLT-VENT is a sintered metal filter on the vent inlet. For particles to get past it: the filter could be degraded, the vent valve opened too quickly (turbulence bypasses the filter), the filter connection could be loose, or venting occurred via a different path that doesn't route through R1-FLT-VENT.

🔢 Step-by-step

1. Timeline: clean → vent → contaminated. Only the vent event occurred. Particles entered during venting.

2. R1-FLT-VENT failure modes (need 2): filter degraded/saturated; vent valve opened too quickly; filter connection loose; venting via cracked flange bypassing the filter.

3. Extended pumpdown: particles add surface area inside R1-CH. More surface area = more adsorbed water and gas = higher surface gas load in the 1–0.1 mbar range. Pumpdown is slow but not stalled.

4. Escalation note: particles observed post-vent; R1-FLT-VENT likely compromised or bypassed; filter inspection and vent procedure confirmation needed before next use.

🔒
Debrief & Teaching Points — available after this session