Module 5

Scenario Cards

Chambers, Components, Valves & System Layout
Facilitator: adjust scaffolding level before distributing

Module 5 Scenario Cards: Chambers, Components, Valves & System Layout

Module: M05 — Chambers, Components, Valves & System Layout Rig Configuration: R1-A (Simple Single-Pump Roughing Rig) and R2-A (Extended System) Cards: SC-M05-01 through SC-M05-03

R1-A Component Reference

Component ID Name Type
R1-CH Chamber Volume
R1-P-RP Roughing Pump Pump
R1-V-VENT Vent Valve Valve
R1-V-ISO Isolation Valve Valve
R1-G-CH Chamber Gauge (Pirani) Gauge
R1-G-BX Barometric Reference Indicator
R1-FLT-VENT Vent Filter (sintered metal) Filter
R1-FLT-EXH Exhaust Filter (oil mist) Filter
R1-L-FL Foreline Line
R1-L-VENT Vent Line Line
R1-L-EXH Exhaust Line Line

R2-A Extended Component Reference

Component ID Name Type
R2-P-HV High-Vacuum Pump (turbo) Pump
R2-P-RP Backing/Roughing Pump Pump
R2-V-GATE Gate Valve (chamber to turbo) Valve
R2-V-ISO Roughing Valve (chamber to roughing pump) Valve
R2-V-FORE Foreline Valve (turbo exhaust to backing pump) Valve
R2-V-VENT Vent Valve Valve
R2-G-CH Chamber Gauge Gauge
R2-G-FL Foreline Gauge Gauge
R2-TRP-FL Foreline Trap Trap
R2-MANF Pumping Manifold Manifold

SC-M05-01: Valve Sequencing Logic — Pump-Down and Vent Sequence on R2-A

Clue: This is a multi-component system. Think about the valve sequence and whether each step was performed correctly.
Guide: Review the pump-down sequence against the three rules. Then check the evidence — if the sequence is correct, the problem lies elsewhere. Consider: gas loads (M02), conductance (M03), materials (M04).

Module: M05 Rig Config: R2-A Competency: M05-COMP-02 Indicators Assessed: M05-IND-02.02, M05-IND-02.03

System State

State Name: SEQUENCING (conceptual pump-down and vent) One-line description: The facilitator presents the R2-A system in a fully vented state and asks students to work through the correct conceptual pump-down sequence, then the correct vent sequence — identifying which valves open and close at each step and explaining why order matters.

Background Information (Provided to Students)

R2-A is a high-vacuum system with two pumps (roughing pump R2-P-RP and turbomolecular pump R2-P-HV), four valves (gate valve R2-V-GATE, roughing valve R2-V-ISO, foreline valve R2-V-FORE, vent valve R2-V-VENT), two gauges (chamber gauge R2-G-CH, foreline gauge R2-G-FL), and a foreline trap (R2-TRP-FL).

The system is currently in the VENTED state: all valves closed, both pumps off, chamber at ~950 mbar.

The target is to pump the system down to high vacuum (below 10-5 mbar), hold at base pressure, then vent back to atmosphere.

Starting Valve Positions

Valve ID Valve Name Position Notes
R2-V-GATE Gate Valve CLOSED Chamber isolated from turbo pump
R2-V-ISO Roughing Valve CLOSED Chamber isolated from roughing pump
R2-V-FORE Foreline Valve CLOSED Turbo exhaust isolated from backing pump
R2-V-VENT Vent Valve CLOSED Chamber isolated from atmosphere

Starting Gauge Readings

Gauge ID Gauge Name Reading Unit What It Tells You
R2-G-CH Chamber Gauge ~950 mbar Chamber at atmospheric pressure
R2-G-FL Foreline Gauge ~950 mbar Foreline at atmospheric pressure (system fully vented)

Pump Status (Starting)

Pump ID Pump Name Status Notes
R2-P-RP Roughing Pump OFF Not running
R2-P-HV Turbo Pump OFF Not running — requires low foreline pressure before starting

Student Prompt

R2-A is presented in the VENTED state. All valves closed, both pumps off, chamber and foreline at ~950 mbar.

Part A — Pump-Down Sequence: 1. Sequence: List the conceptual steps to pump this system from atmosphere to high vacuum. For each step, name: which valve opens or closes, which pump starts, and what would be observed on the gauges. 2. Reasoning: For each step, explain why it happens in that order. Reference the three valve sequencing rules where they apply. 3. Critical decision point: At what gauge reading (approximately) is the roughing valve closed and the gate valve opened? What is this pressure called, and why is it the changeover point?

Part B — Vent Sequence: 4. Sequence: The system is now at base pressure (below 10-5 mbar). List the conceptual steps to safely vent the chamber back to atmosphere. 5. Reasoning: Why must the gate valve to the turbo pump be closed before the vent valve is opened? What would happen if this order were reversed?

Part C — Communication: 6. Write a 3-sentence observation note summarising the pump-down sequence for a shift log. Use component IDs and be specific about the crossover point.

Teaching Points (Facilitator Notes)

Expected pump-down sequence:

Step Action Valve/Pump Change Gauge Expectation Rule Applied
1 Start roughing pump R2-P-RP → ON No immediate gauge change (valves still closed)
2 Open foreline valve R2-V-FORE → OPEN R2-G-FL begins dropping (roughing pump evacuates foreline)
3 Wait for foreline to reach operating pressure Monitor R2-G-FL R2-G-FL drops below ~1 mbar Prepares backing for turbo
4 Start turbo pump R2-P-HV → ON Turbo spins up (takes several minutes to reach speed) Turbo needs low foreline pressure
5 Open roughing valve R2-V-ISO → OPEN R2-G-CH begins dropping — fast viscous flow phase Rough the chamber
6 Rough chamber to crossover pressure Monitor R2-G-CH R2-G-CH drops to ~0.1 mbar
7 Close roughing valve R2-V-ISO → CLOSED R2-G-CH momentarily stable Seal off roughing path
8 Open gate valve R2-V-GATE → OPEN R2-G-CH continues dropping — turbo takes over Rule 1: rough first, then hand off to turbo

Expected vent sequence:

Step Action Valve/Pump Change Gauge Expectation Rule Applied
1 Close gate valve R2-V-GATE → CLOSED R2-G-CH begins slow rise (outgassing) Rule 3: protect turbo from atmosphere
2 Stop turbo pump (begin spin-down) R2-P-HV → OFF (spinning down) Turbo must not be spinning at atmosphere
3 Close foreline valve R2-V-FORE → CLOSED Foreline isolated Protect foreline trap and turbo exhaust side
4 Open vent valve R2-V-VENT → OPEN R2-G-CH rises to ~950 mbar Controlled vent through filter
5 (Once turbo fully stopped and chamber at atmosphere) Stop roughing pump R2-P-RP → OFF R2-G-FL rises to atmosphere

Key learning moments:

Model observation note: "R2-A pump-down: R2-P-RP started, R2-V-FORE opened to evacuate foreline; R2-P-HV started once R2-G-FL confirmed below 1 mbar; R2-V-ISO opened to rough chamber — R2-G-CH dropped from 950 mbar through viscous flow phase to crossover pressure of approximately 0.1 mbar. R2-V-ISO closed, R2-V-GATE opened — R2-P-HV took over, pulling R2-G-CH through molecular flow to base pressure below 10-5 mbar. Crossover from roughing to high-vacuum pumping occurred at 0.1 mbar with no turbo overload."

Common student errors:

SC-M05-02: Feedthrough Leak Path — Diagnosing a Leak at a Motion Feedthrough

Clue: Multiple maintenance actions were performed. Rank them by likelihood of causing the observed problem.
Guide: Consider each action: what could it introduce (moisture, contaminants, seal disturbance)? Match each possibility to the evidence (rate-of-rise pattern, pressure behaviour, timing).

Module: M05 Rig Config: R1-A (conceptually extended with feedthroughs for this scenario) Competency: M05-COMP-01, M05-COMP-02 Indicators Assessed: M05-IND-01.03, M05-IND-02.01, M05-IND-02.02

System State

State Name: ISOLATED (diagnostic hold) One-line description: R1-A (conceptually extended with two feedthroughs on the chamber) has been roughed to base pressure, isolated, and is now under a rate-of-rise test. The test reveals a real leak, and the evidence points to one of the feedthroughs as the source.

Background Information (Provided to Students)

For this scenario, imagine that R1-A's chamber (R1-CH) has been modified for a research application. Two feedthroughs have been added to the chamber:

The system was roughed normally (R1-V-ISO open, R1-V-VENT closed, pump on). The fast phase from 950 to 1 mbar completed in the normal ~90 seconds.

Below 1 mbar, the pump-down slowed more than expected. After 30 minutes, R1-G-CH read 0.15 mbar — the expected base pressure is 0.05 mbar.

The operator isolated the system (R1-V-ISO closed, R1-V-VENT closed, pump off) and performed a rate-of-rise test.

Valve Positions

Valve ID Valve Name Position Why
R1-V-VENT Vent Valve CLOSED Isolated — vent path sealed.
R1-V-ISO Isolation Valve CLOSED Isolated — chamber disconnected from pump.

Gauge Readings

Gauge ID Gauge Name Reading Unit What It Tells You
R1-G-CH Chamber Pirani See rate-of-rise data below mbar Pressure is rising during the isolated hold.
R1-G-BX Barometric Reference ~950 mbar Atmospheric baseline normal.

Rate-of-Rise Test Data

Time after isolation R1-G-CH (mbar) Rate of rise (mbar/min)
0 min 0.15
1 min 0.21 0.06
3 min 0.33 0.06
5 min 0.45 0.06
10 min 0.75 0.06
15 min 1.05 0.06

Additional Information

Pump Status

Pump ID Pump Name Status Notes
R1-P-RP Roughing Pump OFF Pump off for rate-of-rise test. Verified to meet specification independently.

Student Prompt

The rate-of-rise test data from R1-A is shown above. The system failed to reach its normal base pressure.

1. Recognise: Examine the rate of rise for each interval. Is the rate constant, increasing, or decreasing? What type of gas source does this pattern indicate? 2. Interpret: The system has two feedthroughs (FT-1 and FT-2). Based on the rate-of-rise pattern, the maintenance history, and feedthrough design principles, which feedthrough is the most likely source of the leak? Explain your reasoning — name the specific evidence that supports your hypothesis and the evidence that argues against the alternative. 3. Communicate: Write a 3-sentence diagnostic finding. Follow the Week 5 rubric guidance: avoid "it must be..." language, use evidence-based claims, and explicitly name where the chamber is isolated and how that explains the gauge behaviour. 4. Escalate: If this system were being used for a research experiment requiring 0.01 mbar base pressure, what would the impact of this leak be on the planned experiment, and what additional information is needed to confirm the diagnosis before the experiment can proceed?

Teaching Points (Facilitator Notes)

Expected student observations:

Key learning moments:

Model diagnostic finding: "With R1-V-ISO and R1-V-VENT both closed, R1-G-CH shows a constant rate of rise of 0.06 mbar/min over 15 minutes — consistent with a real leak into the isolated chamber zone, not outgassing. The only recent change to the vacuum boundary is the reinstallation of FT-2 (rotary feedthrough, bellows replaced two weeks ago by a trainee). The evidence supports FT-2 as the leading leak source: constant rate indicates a fixed-size opening at the vacuum boundary, and FT-2's recent disassembly and reassembly introduced new seal surfaces that may be improperly seated or damaged."

Research experiment impact: At 0.06 mbar/min leak rate, the system cannot reach 0.01 mbar — the pump would stall at a pressure where the pump speed equals the leak rate divided by the effective speed. The research experiment requiring 0.01 mbar would be impossible.

The evidence indicates FT-2's flange seal and bellows installation as the leading hypothesis. Additional information needed: visual inspection of the gasket condition and bolt torque on FT-2, followed by a confirmation rate-of-rise test, would help confirm the diagnosis.

Common student errors:

SC-M05-03: Isolation Point Identification on a Multi-Zone Coating System

Clue: Think about the system layout. Where in the gas path could this problem originate?
Guide: Map the flow path from chamber to pump. Consider: each connection point, each valve seat, each component boundary. The isolation test data tells you whether the source is inside or outside the sealed volume.

Module: M05 Rig Config: Extended system (based on R2-A principles) Competency: M05-COMP-02 Indicators Assessed: M05-IND-02.01, M05-IND-02.02, M05-IND-02.03

System State

State Name: MULTI-ZONE DIAGNOSTIC One-line description: A multi-zone coating system has three chambers sharing a common pumping manifold. Pressure data from isolated zones is provided. Students must identify all isolation points on the schematic, determine which zone contains the problem, and explain how the isolation points enabled the diagnosis.

Background Information (Provided to Students)

A thin-film coating facility operates a multi-zone vacuum system with the following architecture:

Chambers:

Pumping:

Valves:

Gauges:

System History

The system has been operating normally for three months. Yesterday, a routine maintenance session was performed on Chamber B: the fluid feedthrough (cooling water line) was inspected and re-torqued, and the two electrical feedthroughs were visually checked (no disassembly). The system was re-pumped this morning.

This morning's pump-down: Chambers A and C reached their expected base pressures (0.05 mbar each) within 10 minutes. Chamber B roughed normally from 950 to 1 mbar but then stalled — after 45 minutes, G-B reads 0.30 mbar. The expected base pressure for Chamber B (with the turbo pump) is 5 x 10-6 mbar.

The operator performed a systematic isolation diagnostic.

Isolation Diagnostic Data

Step 1: All isolation valves closed, all vent valves closed, all pumps off.

Zone Gauge Reading at t=0 Reading at t=10 min Rate of rise (mbar/min) Pattern
Chamber A G-A 0.05 0.07 0.002 (decreasing) Normal outgassing
Chamber B G-B 0.30 0.80 0.05 (constant) Constant — real leak
Chamber C G-C 0.05 0.06 0.001 (decreasing) Normal outgassing
Manifold G-M 0.10 0.12 0.002 (decreasing) Normal outgassing

Step 2: Chamber B further investigated — GV-B closed (isolating turbo pump from Chamber B), IV-B closed (isolating manifold from Chamber B), VV-B closed.

Zone Gauge Reading at t=0 Reading at t=10 min Rate of rise (mbar/min) Pattern
Chamber B (isolated from all paths) G-B 0.30 0.80 0.05 (constant) Leak confirmed in Chamber B zone

Valve Positions (During Step 1)

Valve ID Position What It Isolates
IV-A CLOSED Chamber A from manifold
IV-B CLOSED Chamber B from manifold
IV-C CLOSED Chamber C from manifold
IV-M CLOSED Manifold from roughing pump
GV-B CLOSED Chamber B from turbo pump
VV-A CLOSED Chamber A from atmosphere
VV-B CLOSED Chamber B from atmosphere
VV-C CLOSED Chamber C from atmosphere

Student Prompt

The multi-zone coating system schematic and the isolation diagnostic data are presented above.

1. Identify isolation points: List every isolation point in this system. For each one, name the valve, state what two zones it separates, and explain why that separation matters. 2. Interpret the diagnostic data: Using the Step 1 data, which zone contains the problem? What specific evidence supports your conclusion? What does the data tell you about the other zones? 3. Narrow the search: Within Chamber B's boundary, what are the possible leak locations? Rank them from most likely to least likely based on the maintenance history provided. Justify your ranking with evidence — do not list equal probabilities. 4. Communicate: Write a 4-sentence diagnostic report for the facility manager. Follow the Week 5 rubric: use evidence-based claims, explicitly name which isolation points were used and how they explain the gauge behaviour, and avoid "it must be..." language. 5. Escalate: The coating process in Chamber B requires 5 x 10-6 mbar. With the current leak rate of 0.05 mbar/min, can the process proceed? Explain why or why not, referencing the leak rate and the required process pressure.

Teaching Points (Facilitator Notes)

Expected isolation point identification:

Valve Separates Why It Matters
IV-A Chamber A from manifold Allows Chamber A to be vented/loaded without affecting manifold or other chambers
IV-B Chamber B from manifold Isolates the coating chamber for independent diagnostics
IV-C Chamber C from manifold Allows Chamber C to be vented/inspected independently
IV-M Manifold from roughing pump Allows roughing pump to be serviced without venting the manifold
GV-B Chamber B from turbo pump Protects the turbo pump during Chamber B venting and enables independent turbo pump diagnostics
VV-A Chamber A from atmosphere Controls venting of Chamber A
VV-B Chamber B from atmosphere Controls venting of Chamber B
VV-C Chamber C from atmosphere Controls venting of Chamber C

Total: 8 isolation points. Each one defines a zone boundary.

Expected diagnostic interpretation:

Step 1 data conclusively localises the problem:

Step 2 confirms the finding: even with Chamber B fully isolated from all paths (GV-B closed, IV-B closed, VV-B closed), the rate of rise persists at 0.05 mbar/min. The leak is within Chamber B's physical boundary.

Expected leak location ranking within Chamber B:

  1. Fluid feedthrough (cooling water line) — most likely. This feedthrough was physically disturbed yesterday (re-torqued). Re-torquing can damage gaskets, shift seal surfaces, or introduce misalignment. Additionally, fluid feedthroughs carry the catastrophic risk of water ingress if the internal tube fails — though in this case the constant air-leak pattern suggests a flange seal issue, not a tube failure.
  1. Chamber B vent valve seat (VV-B) — possible but less likely. VV-B was not serviced during yesterday's maintenance. However, valve seats can degrade over time (compression set on the O-ring — Module 4 concept). If VV-B's seal is marginal, the system may show a slow leak that mimics an external leak. Lower probability because the timing correlates with the feedthrough maintenance, not with any valve event.
  1. Electrical feedthroughs — unlikely. These were visually inspected but not disassembled. Ceramic-to-metal brazes are static, robust seals. Unless physical damage was introduced during the visual inspection (unlikely), these are low probability.
  1. Chamber wall or weld — very unlikely. Chamber welds that have held for three months do not spontaneously develop leaks. No thermal cycling or mechanical stress events are reported.
  1. Gate valve seat (GV-B) — very unlikely. GV-B was not serviced and has been functioning normally.

Key learning moments:

Model diagnostic report: "Systematic isolation diagnostic on the multi-zone coating system confirms a real leak in Chamber B. With IV-B (manifold isolation), GV-B (turbo pump isolation), and VV-B (vent isolation) all closed, G-B shows a constant rate of rise of 0.05 mbar/min over 10 minutes — while Chambers A, C, and the manifold all show only normal outgassing patterns (decreasing rates below 0.002 mbar/min).

The leak source is within Chamber B's sealed boundary; the fluid feedthrough (cooling water line), which was re-torqued during yesterday's maintenance, is the leading hypothesis based on the timing correlation and the fact that it is the only component whose seal was physically disturbed. Additional information needed: visual inspection of the fluid feedthrough flange seal and gasket condition, followed by a confirmation rate-of-rise test, would help confirm this hypothesis."

Escalation — process impact: The coating process requires 5 x 10-6 mbar. With a constant leak rate of 0.05 mbar/min (50 mbar in approximately 16.7 hours if fully sealed), the leak introduces gas far faster than even a turbo pump can remove at those pressures.

The system will stall at a pressure where the turbo pump's throughput equals the leak throughput — well above the 5 x 10-6 mbar target. The coating process cannot proceed until the leak is repaired. At the current leak rate, the equilibrium pressure would be orders of magnitude above the process requirement.

Common student errors:

End of Scenario Cards — Module 5